House wiring calculator

Under the Philippine Electrical Code, 2.0 mm² wire is limited to 15 A, 3.5 mm² to 20 A and 5.5 mm² to 30 A. A one-storey house with 12 lights, 18 outlets, 2 small aircons and a water heater needs 9 circuits, a 12-branch panel board, 105 lengths of ½" conduit, 2 boxes plus 63 m of 2.0 mm² wire and 4 boxes of 3.5 mm² wire.

Work it out for your own job

Enter your lights, outlets, aircons and other appliances, and Countstruct lays out the circuits, picks the panel board and lists the wire, conduit, boxes, devices and breakers.

Open the electrical rough-in calculator in Countstruct

How to estimate it

  1. Count the circuits

    Lights go on 15 A circuits of at most 8 lights. Outlets go on 20 A circuits of at most 6, with at least 2 for the kitchen and dining area, plus 1 laundry circuit. Each aircon and each large appliance, such as a water heater or pump, gets its own circuit:

    Lighting circuits = ⌈Lights ÷ 8⌉

    Outlet circuits = max(⌈Outlets ÷ 6⌉, 2) + 1 laundry

    Aircons up to 1 HP use 20 A on 3.5 mm² wire; 1.5 to 2.5 HP use 30 A on 5.5 mm².

    The code itself sets no number of outlets per circuit; 8 lights and 6 outlets are planning defaults.

  2. Choose the panel board

    Leave 25% of the spaces spare for future circuits, then round up to a panel size of 4, 6, 8, 12, 16, 20, 24 or 30 branches:

    Spaces = ⌈Circuits × 1.25⌉

  3. Measure the conduit

    Allow 5 m of conduit per point (each light, switch, outlet, aircon or appliance), plus 1.5 m per storey above the first, plus a home run from the panel to each circuit, about 10 m in a small house. Switches default to one per 2 lights. Conduit comes in 3 m lengths, with 10% for bends:

    Lengths of ½" conduit = ⌈Run × 1.10 ÷ 3⌉

  4. Work out the wire

    Each circuit carries 3 wires (line, neutral and ground), with 10% for bends and slack at every box. THHN wire is sold in 150 m boxes; a remainder of 100 m or more is bought as another box, anything less by the metre:

    Wire of each size = Conduit run for that size × 3 × 1.10

  5. Add boxes, devices and breakers

    One utility box per switch, outlet, aircon and appliance; one junction box per light; one breaker per circuit at its rating; one ground rod; and a roll of electrical tape per 4 circuits.

Worked example

A one-storey house with 12 lights, 18 outlets, 2 aircons of 1 HP and a water heater, with a 10 m home run. Switches default to 12 ÷ 2 = 6.

Item Calculation Result
Lighting circuits, 15 A ⌈12 ÷ 8⌉ 2
Outlet circuits, 20 A max(⌈18 ÷ 6⌉, 2) = 3, + 1 laundry 4
Aircon and appliance circuits, 20 A 2 aircons + 1 water heater 3
Panel board ⌈9 × 1.25⌉ = 12 spaces 12 branches
Conduit run Lighting (12 + 6) × 5 + 2 × 10 = 110 m
Outlets 18 × 5 + 3 × 10 = 120 m
Laundry 10 m; aircons and heater 3 × 15 = 45 m
285 m
½" conduit, 3 m 285 × 1.10 ÷ 3 = 104.5 105 lengths
Wire 2.0 mm² 110 × 3 × 1.10 = 363 m 2 boxes + 63 m
Wire 3.5 mm² 175 × 3 × 1.10 = 577.5 m 4 boxes
Utility boxes 6 + 18 + 2 + 1 27
Breakers 2 × 15 A, 7 × 20 A 9

This is a planning estimate. A licensed electrical engineer must design the circuits and sign the plans. The service entrance, meter base, main feeder and load calculation are not included.

What the Countstruct calculator adds

Countstruct electrical rough-in calculator

  • A full circuit schedule from your counts of lights, outlets, aircons and appliances, for 1 to 3 storeys.
  • Wire by size in whole 150 m boxes or by the metre, ½" conduit in 3 m lengths, utility and junction boxes, switches, plates, outlets and breakers.
  • The smallest panel board with 25% spare spaces, and a warning if the panel you pick is too small.
  • Prices from a built-in price book you can edit, and the result goes into a project bill of quantities.
Open the electrical rough-in calculator in Countstruct

Questions

What wire size is used for outlets and lights in the Philippines?

Lighting circuits use 2.0 mm² THHN on a 15 A breaker. Outlet circuits use 3.5 mm² on 20 A. A 1.5 to 2.5 HP aircon uses 5.5 mm² on 30 A. These are the limits in PEC 2.40.1.4(D).

How many outlets can go on one circuit?

The Philippine Electrical Code counts load (180 VA per receptacle), not a fixed number of outlets. Six outlets per 20 A circuit is a common planning default, and it is what the calculator uses.

How long is a box of THHN wire?

150 metres. The calculator buys whole boxes and, when less than 100 m is left over, the rest by the metre.

Does an aircon need its own circuit?

Yes. Each aircon gets its own circuit and breaker: 20 A on 3.5 mm² wire up to 1 HP, 30 A on 5.5 mm² for 1.5 to 2.5 HP.